Communicator Volt (1-10V) Dongle - Settings Overview
Print
Modified on: Fri, 27 Oct, 2023 at 1:38 PM
Basic
Name | Values | Description | Default |
Default Output
|
Output percentage | [0-100]% | Default output percentage. Only works when device is in Smart network and group.
| 100% |
Advanced
Name | Values | Description | Default |
Output range
|
Output voltage (x10) 0% | [0-100] | Output voltage at 0%. Devide setting by 10, meaning 10 will result in 1V at the output.
| 10 |
Output voltage (x10) 100% | [0-100] | Output voltage at 100%. Devide setting by 10, meaning 100 will result in 10V at the output. | 100 |
Smart |
Device network identifier | [1-30] | Smart network ID | 255 (Not set) |
Expert
Name | Values | Description | Default |
Output tuning
|
Scaling factor | 0-1000 | Output tuning value. When 100% output setting does not reach 10V at the output, increase this value.
| 960 |
Force 0 percent to 0 volt | ON/OFF | When receiving a 0% level, set output to 0V even when 'Output voltage (x10) 0%' is not 0.
| OFF |
Did you find it helpful?
Yes
No
Send feedback Sorry we couldn't be helpful. Help us improve this article with your feedback.